Estimated impedance islanding detection method for grids with high motor penetration

Nguyen Duc Tuyen, Goro Fujita, Toshihisa Funabashi, Masakatsu Nomura

Research output: Contribution to journalArticle

1 Citation (Scopus)

Abstract

In the dispersed generation (DG) field, islanding is known as a situation in which those generators are disconnected from the utility feeders and a bunch of local loads being powered by them is isolated. Accordingly, anti-islanding schemes are used to immediately detect the phenomenon in facilitating the detachment of the DG or adaptively controlling the autonomous operation. Negative-sequence impedance measurement is considered as a novel method of detecting electrical islands in DG networks. However, in the case of high induction motor penetration, this method might malfunction. Using two-round impedance measurement, this paper deals with that problem while making typical assessments on how the impedance tolerance values are selected and how these values vary with network configuration. The simulation in PSCAD/EMTDC and experiments validate the methodology.

Original languageEnglish
Pages (from-to)446-455
Number of pages10
JournalIEEJ Transactions on Electrical and Electronic Engineering
Volume8
Issue number5
DOIs
Publication statusPublished - 2013 Sep

Keywords

  • Clarke transformation
  • Impedance measurement
  • Islanding detection
  • Symmetrical transformation

ASJC Scopus subject areas

  • Electrical and Electronic Engineering

Fingerprint Dive into the research topics of 'Estimated impedance islanding detection method for grids with high motor penetration'. Together they form a unique fingerprint.