Fault current limiter based on series active compensator

Takahiro Okawa, Nguyen Xuan Tung, Goro Fujita, Yasutoshi Takemoto, Kazuhiro Horikoshi

研究成果: Conference contribution

3 被引用数 (Scopus)

抄録

Series active compensator (SAC) is a custom compensator utilized in power distribution network, however, due to connected in series with distribution line then SAC would suffer from large current flows due to downstream faults. To limit the flow those fault currents and protect SAC itself as well, a fault current limiting (FCL) function is proposed. Fault current limiting function of SAC will be activated by protection system and then SAC will start injecting a series voltage to the line in such a way to limit fault current to an appropriate level. The contribution of this proposal is the utilization of signals from existing feeder protection system to activate and terminate the FCL. This control simplifies the structure of SAC because the extra build-in fault detection module is not required. Moreover, it will ensure proper coordination between SAC and existing protection systems. Other benefits could be the voltage sag mitigation effect for upstream buses in case fault occurs at downstream section.

本文言語English
ホスト出版物のタイトル2011 26th Annual IEEE Applied Power Electronics Conference and Exposition, APEC 2011
ページ1564-1568
ページ数5
DOI
出版ステータスPublished - 2011 5月 13
イベント26th Annual IEEE Applied Power Electronics Conference and Exposition, APEC 2011 - Fort Worth, TX, United States
継続期間: 2011 3月 62011 3月 10

出版物シリーズ

名前Conference Proceedings - IEEE Applied Power Electronics Conference and Exposition - APEC

Conference

Conference26th Annual IEEE Applied Power Electronics Conference and Exposition, APEC 2011
国/地域United States
CityFort Worth, TX
Period11/3/611/3/10

ASJC Scopus subject areas

  • 電子工学および電気工学

フィンガープリント

「Fault current limiter based on series active compensator」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。

引用スタイル